EN 61643-11 Type 1+2 Surge Protector , 4 Pole Spd PBT Material
Product Details:
Place of Origin: | Dongguan China |
Brand Name: | Uchi |
Certification: | CE / SGS / ISO9001 |
Model Number: | OBV5-B60 |
Payment & Shipping Terms:
Minimum Order Quantity: | 200 piece |
---|---|
Price: | Negotiate |
Packaging Details: | export package / Negotiate |
Delivery Time: | 5-15 days after payment |
Payment Terms: | T/T, L/C, Western Union |
Supply Ability: | 60000 pieces per month |
Detail Information |
|||
Name: | Surge Suppressor,Surge Protection Device | Material: | Nylon,PBT, MOV |
---|---|---|---|
Maximum Continuous Voltage AC: | 275/320/385/440V | Condition: | 100% Original |
CertificationCE,CQC: | CE / CQC / SGS | System Voltage: | 500/600VDC |
Environment Temperature: | (-40℃~+85℃) | Normal Discharge Current(8/20μs): | 30kA |
Status Indicator: | Green(good)/red(need Replacement) | Pole Number: | 1P,2P,3P,4P,3+NPE |
Highlight: | EN 61643-11 4 pole spd,PBT Type 1+2 Surge Protector,EN 61643-11 Type 1+2 Surge Protector |
Product Description
Type 1+2 Surge Protection Device , Surge Suppressor Made With Nylon , PBT , MOV
OBV5-B60 series
The surge arrestors OBV5-B60 meet the type 1+2 requirement class according to IEC 61643-11. These devices protect low-voltage consumer systems from overvoltages of all types and are available in single-pole to four-pole versions. The use of high-performance varistors permits a rapid response time and a low protection level, without any line follow current. If circumstances are uncertain and there is a risk of fire from an overload, the internal cut-off unit disconnects the arrestor from the mains if necessary. In addition, the QR code printed on the arrestor allows disary. In addition, the QR code printed on the arrestor allows direct access to the online installation instructions.
1.High energy surge protection
2.Remote alarm interface
3.Failure detection indicator
4.Standard modular installation
G2060MT: The power line blocks the total power disribution cabinet of the nuildings that are embedded in the ground.
A distribution box with an outside entry and exit line in the building.
Outdoor distribution cabinet/distribution box.
Technical Parameters
Model: OBV5-B60 | |||
Maximum continuous voltage AC | Uc | V | 275/320/385/440 |
SPD to EN 61643-11 | Type 1+2 | ||
SPD to IEC 61643-1 | class I+II | ||
Lightning impulse current (10/350µs) | Iimp | kA | 12,5 |
Nominal discharge current (8/20µs) | In | kA | 30 |
Maximum discharge current (8/20µs) | Imax | kA | 60 |
Voltage protection level | Up | kV | < 1,5/1,8/2,0/2,2 |
Response time | tA | ns | < 25 |
Maximum back-up fuse | A | 125 | |
Temperature range | ϑ | ℃ | -40℃~+85℃ |
Protection rating | IP 20 | ||
Max. cable cross-section flexible (fine-wire) | mm² | 25 | |
Max. cable cross-section rigid (single wire/multi-wire) | mm² | 35 |
Feature:
1,Protect electric system and on-loading electrical apparatus from thunder and instantaneous over-voltage.
2,Protect transmission of Ethernet signals with 48V DC / 34V AC power supply circuits against
lightning induced surges.
3,Enhanced surge protection.
4,For mounting on 35mm DIN rails acc. to EN 60715
5,It can effectively ensure the equipments work properly
Benefits
Easy installation or retrofit
Din-rail mountable
Fail-safe /self-protected designRemote indicator (optional) with 3pin NO/NC contact
IP20 finger-safe designVisual indicator
Small foot print
Others
Technology SPD parameter(Note:According to user requirement ,can be customized Uc=140V,440V,550V,voltage range of range of the SPD):
Type No. | Rated Voltage(V) Un | Continuous Voltage Uc(V~) | Standard Discharge Current In(KA) |
Max Discharge Current Imax(KA) |
Protection Level(KA~) | Response Time(ns) |
DGM1(2)-D5 | 220/380 |
275/320 385/420 |
5 | 10 | 1.2 | ≤25 |
DGM1(2)-D10 | 10 | 2 | 1.6 | |||
DGM1(2)-C20 | 20 | 40 | 1.8 | |||
DGM13-B30 | 30 | 60 | .2.2 | |||
DGM3(4)-B40 | 10 | 80 | 2.4 | |||
DGM(4)-B60 | 60 | 100 | 2.8 | |||
DGM-N-PE | 220/255 | 40/60 | 60/80 | 1.2 | ≤100 |