56V DC Surge Protection Device 40KA For DC Electrical Distribution System
Product Details:
| Place of Origin: | Dongguan China |
| Brand Name: | Uchi |
| Certification: | CE / SGS / ISO900 |
| Model Number: | DC Surge Protection Device |
Payment & Shipping Terms:
| Minimum Order Quantity: | 50 Piece/Pieces |
|---|---|
| Price: | Negotiate Ex-work / FOB price |
| Packaging Details: | Export package |
| Delivery Time: | Shipped in 10 days after payment |
| Payment Terms: | TT / LC |
| Supply Ability: | 100000 Piece/Pieces Month |
|
Detail Information |
|||
| Pole Number: | 1 Pole | Un: | 24VDC |
|---|---|---|---|
| Uc: | 56VDC | In: | 20KA |
| Imax: | 40KA | Material: | Thermal Plastic |
| Classification: | Class II | Protection Class IP: | IP 20 |
| Application: | DC Power Supply System | Test Standards: | IEC 61643-21 |
| Highlight: | surge arrester 40ka,40ka DC Surge Protection Device,56V DC Surge Protection Device |
||
Product Description
40KA 56vdc Surge Protection Device For DC Power Supply System
Performance characteristics:
Adopt the latest thermal separation technology, built-in thermal protection, automatic separation device for short-circuit failure, completely avoid fire;The core components adopt internationally well-known brands, with excellent performance, stable and reliable work;
The main parameters:
Operating Voltage : 24V DC
Nominal discharge current In(8/20μs): 20kA
Maximum discharge current Imax (8/20μs): 40kA
Combination method: +/PE,-/PE
Response time: ≤25ns
Working environment: -40℃~+80℃
Installation method: rail installation
Place of Origin: Dongguan
Qualification certification: CE, FCC, ROHS, product test report, Pacific Product Insurance, etc.
Test standard: IEC 61643-1:2005; GB 18802.1-2011 Low Voltage Surge Protector (SPD) Part 1 Surge Protector for Low Voltage Distribution System-Performance Requirements and Test Methods
Scope of application:
This product is a special lightning surge protector for DC systems, suitable for 12V DC power supply systems.
| DC Surge Protection Device | |
| SPD classification according to EN61643-11 | Type 2 |
| SPD classification according to IEC61643-11 | Class II |
| Applicable Power Supply System | DC Power Supply System |
| Nominal voltage Un | DC 24V |
| Max. continuous operating voltage Uc | DC 56V |
| Nominal discharge current (8/20us) In | 20kA |
| Maximum Discharge Current (8/20µs) Imax | 40kA |
| Leakage Current | ≤20uA |
| Voltage protection level Up | ≤600V |
| Response time tA | ≤25ns |
| Operating temperature range Tu | -40℃-80℃ |
| Relative Humidity | ≤95%RH |
| Operating state / fault indication | green / red |
| Cross-section area (Min.) | 2.5mm2 |
| Cross-section area (Max.) | 16mm2 |
| Protection Mode | "+"-PE, "-"-PE |
| For mounting on | 35mm Din rail |
| Enclosure material | Thermal plastic UL94-V0 |
| Degree of protection | IP20 |
| Remote Alarm Function | Optional |
More application
Q: Can I get some samples?
A: Yes, Sample orders welcomed.
Q: Can I use my own Logo or design on goods?
A: Yes, Customized logo and design on mass production are available.
Q:What is the delivery time?
A: 3 days for samples, 7-15 days for mass production.
Q: What is the payment term?
A: T/T, L/C at sight, West union , Paypal, etc.